faultInfo = [
|
|
'''\
|
|
Fault Number: 0
|
|
Description: GFDI fault (grounded DC)
|
|
Selector Values:
|
|
0x01 = GFDI fault detected
|
|
0x10 = Loss of communication
|
|
Severity: 0x110 = Lockdown
|
|
''',
|
|
'''\
|
|
Fault Number: 1
|
|
Description: IMI fault (floating DC)
|
|
Selector Values: NA
|
|
Severity: 0x110 = Lockdown
|
|
''',
|
|
'''\
|
|
Fault Number: 2
|
|
Description: Power module heatsink temperature fault
|
|
Selector Values:
|
|
0x00 = Over temperature
|
|
0x01 = Under temperature
|
|
Severity: 0x100 Abort 1
|
|
''',
|
|
'''\
|
|
Fault Number: 3
|
|
Description: Control board temperature fault
|
|
Selector Values:
|
|
0x00 = Over temperature
|
|
0x01 = Under temperature
|
|
Severity: 0x100 Abort 1
|
|
''',
|
|
'''\
|
|
Fault Number: 4
|
|
Description: 24V auxiliary supply under voltage
|
|
Selector Values: NA
|
|
Severity: 0x100 Abort 1
|
|
''',
|
|
'''\
|
|
Fault Number: 5
|
|
Description: Fan fault
|
|
Selector Values:
|
|
0x00 = Fan not spinning
|
|
0x01 = Bad tach reading
|
|
Severity: 0x110 = Lockdown
|
|
''',
|
|
'''\
|
|
Fault Number: 6
|
|
Description: DC differential over voltage
|
|
Selector Values:
|
|
0x00 = Port 2
|
|
0x01 = Port 3
|
|
Severity: 0x100 Abort 1
|
|
''',
|
|
'''\
|
|
Fault Number: 7
|
|
Description: DC differential under voltage
|
|
Selector Values:
|
|
0x00 = Port 2
|
|
0x01 = Port 3
|
|
Severity: 0x100 Abort 1
|
|
''',
|
|
'''\
|
|
Fault Number: 8
|
|
Description: Link over voltage
|
|
Selector Values: NA
|
|
Severity: 0x101 Abort 2
|
|
''',
|
|
'''\
|
|
Fault Number: 9
|
|
Description: Link starving
|
|
Selector Values: NA
|
|
Severity: 0x101 Abort 2
|
|
''',
|
|
'''\
|
|
Fault Number: 10
|
|
Description: Link over current
|
|
Selector Values: NA
|
|
Severity: 0x101 Abort 2
|
|
''',
|
|
'''\
|
|
Fault Number: 11
|
|
Description: IGBT VCES over voltage 1
|
|
Selector Values:
|
|
0x00 = Link positive to phase A
|
|
0x01 = Link positive to phase B
|
|
0x10 = Link positive to phase C
|
|
Severity: 0x101 Abort 2
|
|
''',
|
|
'''\
|
|
Fault Number: 12
|
|
Description: IGBT VCES over voltage 2
|
|
Selector Values:
|
|
0x00 = Link negative to phase A
|
|
0x01 = Link negative to phase B
|
|
0x10 = Link negative to phase C
|
|
Severity: 0x101 Abort 2
|
|
''',
|
|
'''\
|
|
Fault Number: 13
|
|
Description: IGBT VCES over voltage 3
|
|
Selector Values:
|
|
0x00 = Link positive to DC port 2
|
|
0x01 = Link positive to DC port 3
|
|
0x10 = Link positive to DC common
|
|
Severity: 0x101 Abort 2
|
|
''',
|
|
'''\
|
|
Fault Number: 14
|
|
Description: IGBT VCES over voltage 4
|
|
Selector Values:
|
|
0x00 = Link positive to DC port 2
|
|
0x01 = Link positive to DC port 3
|
|
0x10 = Link positive to DC common
|
|
Severity: 0x101 Abort 2
|
|
''',
|
|
'''\
|
|
Fault Number: 15
|
|
Description: AC A-B hard switch
|
|
Selector Values: 0x00, 0x01, 0x10, 0x11
|
|
Severity: 0x101 Abort 2
|
|
''',
|
|
'''\
|
|
Fault Number: 16
|
|
Description: AC B-C hard switch
|
|
Selector Values: 0x00, 0x01, 0x10, 0x11
|
|
Severity: 0x101 Abort 2
|
|
''',
|
|
'''\
|
|
Fault Number: 17
|
|
Description: AC C-A hard switch
|
|
Selector Values: 0x00, 0x01, 0x10, 0x11
|
|
Severity: 0x101 Abort 2
|
|
''',
|
|
'''\
|
|
Fault Number: 18
|
|
Description: DC2 input hard switch
|
|
Selector Values: 0x00, 0x01, 0x10, 0x11
|
|
Severity: 0x101 Abort 2
|
|
''',
|
|
'''\
|
|
Fault Number: 19
|
|
Description: DC2 output hard switch
|
|
Selector Values: 0x00, 0x01, 0x10, 0x11
|
|
Severity: 0x101 Abort 2
|
|
''',
|
|
'''\
|
|
Fault Number: 20
|
|
Description: DC3 input hard switch
|
|
Selector Values: 0x00, 0x01, 0x10, 0x11
|
|
Severity: 0x101 Abort 2
|
|
''',
|
|
'''\
|
|
Fault Number: 21
|
|
Description: DC3 output hard switch
|
|
Selector Values: 0x00, 0x01, 0x10, 0x11
|
|
Severity: 0x101 Abort 2
|
|
''',
|
|
'''\
|
|
Fault Number: 22
|
|
Description: Link state timer check
|
|
Selector Values: NA
|
|
Severity: 0x101 Abort 2
|
|
''',
|
|
'''\
|
|
Fault Number: 23
|
|
Description: Bad link start
|
|
Selector Values: 0x00, 0x01, 0x10, 0x11
|
|
Severity: 0x101 Abort 2
|
|
''',
|
|
'''\
|
|
Fault Number: 24
|
|
Description: Invalid method/settings
|
|
Selector Values:
|
|
0x00 = Invalid port1 method/setting
|
|
0x01 = Invalid port2 method/setting
|
|
0x10 = Invalid port3 method/setting
|
|
Severity: 0x101 Abort 2
|
|
''',
|
|
'''\
|
|
Fault Number: 25
|
|
Description: Island detected
|
|
Selector Values: NA
|
|
Severity: 0x011 Abort 0
|
|
''',
|
|
'''\
|
|
Fault Number: 26
|
|
Description: AC under voltage level 1 trip
|
|
Selector Values: NA
|
|
Severity: 0x011 Abort 0
|
|
''',
|
|
'''\
|
|
Fault Number: 27
|
|
Description: AC under voltage level 2 trip
|
|
Selector Values: NA
|
|
Severity: 0x011 Abort 0
|
|
''',
|
|
'''\
|
|
Fault Number: 28
|
|
Description: AC under voltage level 3 trip
|
|
Selector Values: NA
|
|
Severity: 0x011 Abort 0
|
|
''',
|
|
'''\
|
|
Fault Number: 29
|
|
Description: AC under voltage level 4 trip
|
|
Selector Values: NA
|
|
Severity: 0x011 Abort 0
|
|
''',
|
|
'''\
|
|
Fault Number: 30
|
|
Description: AC over voltage level 1 trip
|
|
Selector Values: NA
|
|
Severity: 0x011 Abort 0
|
|
''',
|
|
'''\
|
|
Fault Number: 31
|
|
Description: AC over voltage level 2 trip
|
|
Selector Values: NA
|
|
Severity: 0x011 Abort 0
|
|
''',
|
|
'''\
|
|
Fault Number: 32
|
|
Description: AC over voltage level 3 trip
|
|
Selector Values: NA
|
|
Severity: 0x011 Abort 0
|
|
''',
|
|
'''\
|
|
Fault Number: 33
|
|
Description: AC over voltage level 4 trip
|
|
Selector Values: NA
|
|
Severity: 0x011 Abort 0
|
|
''',
|
|
'''\
|
|
Fault Number: 34
|
|
Description: AC under frequency level 1 trip
|
|
Selector Values: NA
|
|
Severity: 0x011 Abort 0
|
|
''',
|
|
'''\
|
|
Fault Number: 35
|
|
Description: AC under frequency level 2 trip
|
|
Selector Values: NA
|
|
Severity: 0x011 Abort 0
|
|
''',
|
|
'''\
|
|
Fault Number: 36
|
|
Description: AC under frequency level 3 trip
|
|
Selector Values: NA
|
|
Severity: 0x011 Abort 0
|
|
''',
|
|
'''\
|
|
Fault Number: 37
|
|
Description: AC under frequency level 4 trip
|
|
Selector Values: NA
|
|
Severity: 0x011 Abort 0
|
|
''',
|
|
'''\
|
|
Fault Number: 38
|
|
Description: AC over frequency level 1 trip
|
|
Selector Values: NA
|
|
Severity: 0x011 Abort 0
|
|
''',
|
|
'''\
|
|
Fault Number: 39
|
|
Description: AC over frequency level 2 trip
|
|
Selector Values: NA
|
|
Severity: 0x011 Abort 0
|
|
''',
|
|
'''\
|
|
Fault Number: 40
|
|
Description: AC over frequency level 3 trip
|
|
Selector Values: NA
|
|
Severity: 0x011 Abort 0
|
|
''',
|
|
'''\
|
|
Fault Number: 41
|
|
Description: AC over frequency level 4 trip
|
|
Selector Values: NA
|
|
Severity: 0x011 Abort 0
|
|
''',
|
|
'''\
|
|
Fault Number: 42
|
|
Description: Watchdog timeout
|
|
Selector Values: 0x00, 0x01
|
|
Severity: 0x101 Abort 2
|
|
''',
|
|
'''\
|
|
Fault Number: 43
|
|
Description: Emergency stop active
|
|
Selector Values: NA
|
|
Severity: 0x011 = Abort 0
|
|
''',
|
|
'''\
|
|
Fault Number: 44
|
|
Description: Sensing fault
|
|
Selector Values: NA
|
|
Severity: 0x101 Abort 2
|
|
''',
|
|
'''\
|
|
Fault Number: 45
|
|
Description: Arc fault
|
|
Selector Values: NA
|
|
Severity: 0x011 Abort 0
|
|
''',
|
|
'''\
|
|
Fault Number: 46
|
|
Description: Comms processor initiated shutdown
|
|
Selector Values: NA
|
|
Severity: 0x101 Abort 2
|
|
''',
|
|
'''\
|
|
Fault Number: 47
|
|
Description: Surge detect
|
|
Selector Values:
|
|
0x00 = Phase A
|
|
0x01 = Phase B
|
|
0x10 = Phase C
|
|
Severity: 0x100 Abort 1
|
|
''',
|
|
'''\
|
|
Fault Number: 48
|
|
Description: AC switch breakdown voltage exceeded
|
|
Selector Values:
|
|
0x00 = Phase A to phase B
|
|
0x01 = Phase B to phase C
|
|
0x10 = Phase C to phase A
|
|
Severity: 0x101 Abort 2
|
|
''',
|
|
'''\
|
|
Fault Number: 49
|
|
Description: DC switch breakdown voltage exceeded
|
|
Selector Values:
|
|
0x00 = DC2
|
|
0x01 = DC3
|
|
Severity: 0x101 Abort 2
|
|
''',
|
|
'''\
|
|
Fault Number: 50
|
|
Description: Precharge timeout
|
|
Selector Values: NA
|
|
Severity: 0x101 Abort 2
|
|
''',
|
|
'''\
|
|
Fault Number: 51
|
|
Description: AC to link primary high voltage
|
|
Selector Values:
|
|
0x000 = Positive to ground
|
|
0x001 = Negative to ground
|
|
Severity: 0x101 Abort 2
|
|
''',
|
|
'''\
|
|
Fault Number: 52
|
|
Description: AC line to line instantaneous over voltage
|
|
Selector Values:
|
|
0x000 = Phase A to phase B
|
|
0x001 = Phase B to phase C
|
|
0x010 = Phase C to phase A
|
|
Severity: 0x100 Abort 1
|
|
''',
|
|
'''\
|
|
Fault Number: 53
|
|
Description: License fault
|
|
Selector Values: NA
|
|
Severity: 0x101 Abort 2
|
|
''',
|
|
'''\
|
|
Fault Number: 54
|
|
Description: Grid_Ack timeout
|
|
Selector Values: NA
|
|
Severity: 0x100 Abort 1
|
|
'''
|
|
] |