faultInfo = [ '''\ Fault Number: 0 Description: GFDI fault (grounded DC) Selector Values: 0x01 = GFDI fault detected 0x10 = Loss of communication Severity: 0x110 = Lockdown ''', '''\ Fault Number: 1 Description: IMI fault (floating DC) Selector Values: NA Severity: 0x110 = Lockdown ''', '''\ Fault Number: 2 Description: Power module heatsink temperature fault Selector Values: 0x00 = Over temperature 0x01 = Under temperature Severity: 0x100 Abort 1 ''', '''\ Fault Number: 3 Description: Control board temperature fault Selector Values: 0x00 = Over temperature 0x01 = Under temperature Severity: 0x100 Abort 1 ''', '''\ Fault Number: 4 Description: 24V auxiliary supply under voltage Selector Values: NA Severity: 0x100 Abort 1 ''', '''\ Fault Number: 5 Description: Fan fault Selector Values: 0x00 = Fan not spinning 0x01 = Bad tach reading Severity: 0x110 = Lockdown ''', '''\ Fault Number: 6 Description: DC differential over voltage Selector Values: 0x00 = Port 2 0x01 = Port 3 Severity: 0x100 Abort 1 ''', '''\ Fault Number: 7 Description: DC differential under voltage Selector Values: 0x00 = Port 2 0x01 = Port 3 Severity: 0x100 Abort 1 ''', '''\ Fault Number: 8 Description: Link over voltage Selector Values: NA Severity: 0x101 Abort 2 ''', '''\ Fault Number: 9 Description: Link starving Selector Values: NA Severity: 0x101 Abort 2 ''', '''\ Fault Number: 10 Description: Link over current Selector Values: NA Severity: 0x101 Abort 2 ''', '''\ Fault Number: 11 Description: IGBT VCES over voltage 1 Selector Values: 0x00 = Link positive to phase A 0x01 = Link positive to phase B 0x10 = Link positive to phase C Severity: 0x101 Abort 2 ''', '''\ Fault Number: 12 Description: IGBT VCES over voltage 2 Selector Values: 0x00 = Link negative to phase A 0x01 = Link negative to phase B 0x10 = Link negative to phase C Severity: 0x101 Abort 2 ''', '''\ Fault Number: 13 Description: IGBT VCES over voltage 3 Selector Values: 0x00 = Link positive to DC port 2 0x01 = Link positive to DC port 3 0x10 = Link positive to DC common Severity: 0x101 Abort 2 ''', '''\ Fault Number: 14 Description: IGBT VCES over voltage 4 Selector Values: 0x00 = Link positive to DC port 2 0x01 = Link positive to DC port 3 0x10 = Link positive to DC common Severity: 0x101 Abort 2 ''', '''\ Fault Number: 15 Description: AC A-B hard switch Selector Values: 0x00, 0x01, 0x10, 0x11 Severity: 0x101 Abort 2 ''', '''\ Fault Number: 16 Description: AC B-C hard switch Selector Values: 0x00, 0x01, 0x10, 0x11 Severity: 0x101 Abort 2 ''', '''\ Fault Number: 17 Description: AC C-A hard switch Selector Values: 0x00, 0x01, 0x10, 0x11 Severity: 0x101 Abort 2 ''', '''\ Fault Number: 18 Description: DC2 input hard switch Selector Values: 0x00, 0x01, 0x10, 0x11 Severity: 0x101 Abort 2 ''', '''\ Fault Number: 19 Description: DC2 output hard switch Selector Values: 0x00, 0x01, 0x10, 0x11 Severity: 0x101 Abort 2 ''', '''\ Fault Number: 20 Description: DC3 input hard switch Selector Values: 0x00, 0x01, 0x10, 0x11 Severity: 0x101 Abort 2 ''', '''\ Fault Number: 21 Description: DC3 output hard switch Selector Values: 0x00, 0x01, 0x10, 0x11 Severity: 0x101 Abort 2 ''', '''\ Fault Number: 22 Description: Link state timer check Selector Values: NA Severity: 0x101 Abort 2 ''', '''\ Fault Number: 23 Description: Bad link start Selector Values: 0x00, 0x01, 0x10, 0x11 Severity: 0x101 Abort 2 ''', '''\ Fault Number: 24 Description: Invalid method/settings Selector Values: 0x00 = Invalid port1 method/setting 0x01 = Invalid port2 method/setting 0x10 = Invalid port3 method/setting Severity: 0x101 Abort 2 ''', '''\ Fault Number: 25 Description: Island detected Selector Values: NA Severity: 0x011 Abort 0 ''', '''\ Fault Number: 26 Description: AC under voltage level 1 trip Selector Values: NA Severity: 0x011 Abort 0 ''', '''\ Fault Number: 27 Description: AC under voltage level 2 trip Selector Values: NA Severity: 0x011 Abort 0 ''', '''\ Fault Number: 28 Description: AC under voltage level 3 trip Selector Values: NA Severity: 0x011 Abort 0 ''', '''\ Fault Number: 29 Description: AC under voltage level 4 trip Selector Values: NA Severity: 0x011 Abort 0 ''', '''\ Fault Number: 30 Description: AC over voltage level 1 trip Selector Values: NA Severity: 0x011 Abort 0 ''', '''\ Fault Number: 31 Description: AC over voltage level 2 trip Selector Values: NA Severity: 0x011 Abort 0 ''', '''\ Fault Number: 32 Description: AC over voltage level 3 trip Selector Values: NA Severity: 0x011 Abort 0 ''', '''\ Fault Number: 33 Description: AC over voltage level 4 trip Selector Values: NA Severity: 0x011 Abort 0 ''', '''\ Fault Number: 34 Description: AC under frequency level 1 trip Selector Values: NA Severity: 0x011 Abort 0 ''', '''\ Fault Number: 35 Description: AC under frequency level 2 trip Selector Values: NA Severity: 0x011 Abort 0 ''', '''\ Fault Number: 36 Description: AC under frequency level 3 trip Selector Values: NA Severity: 0x011 Abort 0 ''', '''\ Fault Number: 37 Description: AC under frequency level 4 trip Selector Values: NA Severity: 0x011 Abort 0 ''', '''\ Fault Number: 38 Description: AC over frequency level 1 trip Selector Values: NA Severity: 0x011 Abort 0 ''', '''\ Fault Number: 39 Description: AC over frequency level 2 trip Selector Values: NA Severity: 0x011 Abort 0 ''', '''\ Fault Number: 40 Description: AC over frequency level 3 trip Selector Values: NA Severity: 0x011 Abort 0 ''', '''\ Fault Number: 41 Description: AC over frequency level 4 trip Selector Values: NA Severity: 0x011 Abort 0 ''', '''\ Fault Number: 42 Description: Watchdog timeout Selector Values: 0x00, 0x01 Severity: 0x101 Abort 2 ''', '''\ Fault Number: 43 Description: Emergency stop active Selector Values: NA Severity: 0x011 = Abort 0 ''', '''\ Fault Number: 44 Description: Sensing fault Selector Values: NA Severity: 0x101 Abort 2 ''', '''\ Fault Number: 45 Description: Arc fault Selector Values: NA Severity: 0x011 Abort 0 ''', '''\ Fault Number: 46 Description: Comms processor initiated shutdown Selector Values: NA Severity: 0x101 Abort 2 ''', '''\ Fault Number: 47 Description: Surge detect Selector Values: 0x00 = Phase A 0x01 = Phase B 0x10 = Phase C Severity: 0x100 Abort 1 ''', '''\ Fault Number: 48 Description: AC switch breakdown voltage exceeded Selector Values: 0x00 = Phase A to phase B 0x01 = Phase B to phase C 0x10 = Phase C to phase A Severity: 0x101 Abort 2 ''', '''\ Fault Number: 49 Description: DC switch breakdown voltage exceeded Selector Values: 0x00 = DC2 0x01 = DC3 Severity: 0x101 Abort 2 ''', '''\ Fault Number: 50 Description: Precharge timeout Selector Values: NA Severity: 0x101 Abort 2 ''', '''\ Fault Number: 51 Description: AC to link primary high voltage Selector Values: 0x000 = Positive to ground 0x001 = Negative to ground Severity: 0x101 Abort 2 ''', '''\ Fault Number: 52 Description: AC line to line instantaneous over voltage Selector Values: 0x000 = Phase A to phase B 0x001 = Phase B to phase C 0x010 = Phase C to phase A Severity: 0x100 Abort 1 ''', '''\ Fault Number: 53 Description: License fault Selector Values: NA Severity: 0x101 Abort 2 ''', '''\ Fault Number: 54 Description: Grid_Ack timeout Selector Values: NA Severity: 0x100 Abort 1 ''' ]