campbell-cr10-logging/data-logger-program/test2-comments.DLD
2020-11-29 14:34:40 -08:00

116 lines
1.9 KiB
Text

};CR10
;test2.DLD
;Created by Short Cut (4.3)
;$
;:BattV :ProgSig :RTemp_C :Temp_C :Temp_C_1
;:Temp_C_2 :Temp_C_3 :Temp_C_4 :Temp_C_5 :Temp_C_6
;:Temp_C_7 :Temp_C_8 :Temp_C_9 :Temp_C_10:Temp_C_11
;:Temp_C_12:Temp_C_13:Temp_C_14:Temp_C_15:Temp_C_16
;:Temp_C_17:Temp_C_18:Temp_C_19:Temp_C_20:Temp_C_21
;:Temp_C_22:Temp_C_23:Temp_C_24
;$
;%
;Final Storage Label File for: test2.SCW
;Date: 9/28/2020
;Time: 19:47:37
;
;Estimated final storage locations used per day: 0
;%
MODE 1 ; Program Table 1
SCAN RATE 1.0000 ; Execution interval
1:P10
1:1
2:P92 ; IF TIME
1:0
2:1440
3:30 ; DO
3:P19 ; Move Program Signature to
1:2 ; Location
4:P95 ; END
5:P86 ; DO Command
1:42 ; Set Port 2 High
6:P6 ; Full bridge with single differential measurement
1:1 ; Reps
2:23 ; Range
3:1 ; Differential channel number
4:1 ; Excitation channel number
5:1200 ; Excitation voltage (mV)
6:3 ; Location
7:-0.001 ; Multiplier
8:0.09707 ; Offset
7:P59 ; Bridge Transform
1:1 ;
2:3
3:10.025
8:P16
1:1
2:3
3:3
4:1
5:0
9:P87 ; LOOP
1:0 ; Delay
2:25 ; Count
10:P86 ; DO
1:71 ; Pulse port 1
11:P22 ; Excitation with delay
1:1
2:0
3:1
4:0
12:P86 ; DO
1:71 ; Pulse port 1
13:P22 ; Excitation with delay
1:1
2:0
3:1
4:0
14:P14 ; Thermocouple temperature differential measurement
1:1 ; Reps
2:21 ; Range
3:1 ; Differential channel number
4:3 ; Thermocouple type
5:3 ; Reference temperature location
6:4-- ; Destination location
7:1 ; Multiplier
8:0 ; Offset
15:P95 ; END LOOP
16:P86 ; DO
1:52 ; Set Port 2 Low
MODE 2
SCAN RATE 10.0000
1:P96
1:71
MODE 3
MODE 10
1:28
2:102
3:0
MODE 12
1:0000
2:0000
3:0000